Air Conditioning Size Calculator

Compare an indicative ducted or split-system screening estimate. A qualified site assessment is still needed before selecting equipment.

Property Details
Enter your specifications for precise sizing.

Enter the ducted details for an area-based screening estimate. The result is not an equipment specification or an assessment of your property's actual heating and cooling loads.

Define the spaces before using a floor-area estimate

A property's advertised floor area can include rooms and ancillary spaces you do not intend to condition. Start with a marked plan of the occupied spaces, then identify which doors are normally closed and where air could return. A single split-system head is not a duct network, and a ducted outlet count does not establish the thermal demand of each room. Keep the proposed room boundaries with your estimate so an assessor can see what the number represents.

The assumptions this screening tool actually uses

For ducted screening, the good, average and poor insulation selections use 120, 135 and 150 W/m² respectively; split screening uses 110, 125 and 140 W/m². The ceiling-height choices of 2.7 m and 3.0 m apply multipliers of 1.08 and 1.15. Selecting west-facing windows applies 1.08; the double-storey choice applies 1.10 in ducted mode only. These are this site's simplified screening assumptions, not an engineering standard or a measured insulation rating. The suburb, bedroom count and room description do not alter these factors.

What the tool does not measure

A dropdown cannot measure glazing area, window shading, building leakage, envelope construction, internal gains or the operating conditions of a particular outdoor unit. This tool also does not calculate separate winter heating loads, humidity control, duct pressure losses or the performance of a zoning arrangement. It does not turn a suburb name into property-specific weather data. Take the estimate to a qualified assessor with plans and equipment requirements instead of treating it as a completed design.

Keep the screening result separate from an installed quote

The displayed capacity step is a way of grouping the estimate within the tool's limited list, not an instruction to round up and purchase that equipment. An available starting package price does not confirm access, electrical work, drainage, duct routes, permissions or compatibility with retained components. If the estimate exceeds the list, a price for the maximum listed step is not a quote for the unassessed demand. Agree the actual model combination and installed scope after assessment.

Read the Australian Government's heating and cooling guidance for general equipment-selection and building-efficiency advice. It does not certify this site's screening coefficients.

Questions about this calculator

Which floor area should I enter?

Use the area you intend to condition, not automatically the total advertised property area. Exclude garages, unconditioned storage and other spaces outside the proposed system. For a split system, assess the intended room or connected space rather than assuming a head will distribute air through every closed door.

Does my suburb or bedroom count change the calculation?

No. Those fields describe the enquiry but do not select a weather file or modify this tool's area-based estimate. The calculation uses the selected system type, area, insulation category, ceiling-height category and west-facing-window choice, plus the storey choice for ducted systems. A real assessment needs more detailed building and climate inputs.

Is the displayed capacity an equipment recommendation?

No. It is the next displayed screening step at or above the tool's calculated estimate, not proof that a particular model will meet your heating and cooling needs. An assessor must check room loads, permitted operating ranges, airflow and the actual installation. Do not automatically buy a larger unit to compensate for missing design information.

What happens if the estimate exceeds the displayed range?

The tool reports that the estimate is outside its displayed range and does not show a package price as though the largest listed system meets that demand. Request an assessment rather than treating the display limit as a suitable capacity or assuming that several indoor units can share any outdoor unit.